SE3000 Dissolved Gas Analysis Online Monitoring Device

SE3000 Dissolved Gas Analysis Online Monitoring Device is designed to analyze key gases dissolved in transformer insulating oil.

Product Presentation

By continuously detecting and diagnosing incipient internal faults through gas content analysis, it provides real-time insights into equipment health. This effectively overcomes the limitations of long turnaround times associated with traditional laboratory chromatography.

Utilizing advanced gas chromatography technology, the SE3000 rapidly and accurately measures the concentrations of all critical dissolved gases—including H₂, CO, CO₂, CH₄, C₂H₂, C₂H₄, and C₂H₆- directly on-site. An integrated expert system intelligently diagnoses potential latent faults based on this data. It is suitable for monitoring oil-filled high-voltage equipment such as transformers and reactors rated at 35kV and above. Optional functions include monitoring moisture content in oil, core/clamp ground current, ambient temperature, and additional gases like O₂ and N₂.

Product Feature

Technical Specifications

Working Environment Temperature-40 ~ +45 ℃
Working Environment Humidity5% ~ 95% RH
Atmospheric Pressure80 ~ 110 kPa
Working VoltageAC 220V (1 ± 10%) V, 50 Hz
Power Waste1.5 kW (Excluding Tropical Belt)
Inspection Cycle< 2 hours, Fast Mode ≤ 30 minutes
Repetitiveness< 3%
Communication InterfaceOptical Ethernet, Ethernet Port, RS-485
Hydrogen (H₂)2 ~ 20*± 2 μL/L or ± 30%
20 ~ 1000± 30%
Acetylene (C₂H₂)0.2 ~ 5*± 0.2 μL/L or ± 30%
5 ~ 10± 30%
10 ~ 50± 20%
CH₄, C₂H₆, C₂H₄0.5 ~ 10*± 0.5 μL/L or ± 30%
10 ~ 150± 30%
Carbon Monoxide (CO)25 ~ 100*± 25 μL/L or ± 30%
100 ~ 1500± 30%
Carbon Dioxide (CO₂)25 ~ 200*± 25 μL/L or ± 30%
100 ~ 7500± 30%
Total Hydrocarbons (C1+C2)2 ~ 10*± 2 μL/L or ± 30%
10 ~ 150± 30%
150 ~ 500± 20%
Water Content in Oil1 ~ 100 μL/L± 10%
Grounding Current of Iron Core/Clamp1 mA ~ 30 A± 3% or ± 1 mA (whichever is greater)