As a part of the SAS, it works as a station communication manager, which collects, stores and maps signals of relays, measurement units, control units and other IEDs in the substation to higher-level systems such as control center (CC) and distributed control system (DCS).
The PRS-7910 supports several protocols, such as IEC 61850, IEC 60870-5-101/104, IEC 60870-5-103, Modbus and DNP3.0. Data can be transmitted to and received from analog channel, digital channel or network connected to CC, DCS or other system. The direct transmission mode and the device independent avoid any interaction or influence with the substation SCADA (Supervisory Control and Data Acquisition) system.
Furthermore, the PRS-7910 can run as a data acquisition and logic treatment platform and provides various and flexible advanced function extensions.
Utilizes a quad-core CPU and SSD storage, with a fully enclosed steel chassis to enhance anti-interference capabilities, and supports power supply redundancy modules.
Features a built-in history database with an optional capacity of 128-256GB, supporting storage of historical SOE, reports, fault recordings, and other data types.
Both server and client support standard protocols including IEC, DNP, Modbus, as well as advanced IEC 61850 and customized protocols.
Compatible with IEC 61850/103 standards, supports models such as primary and secondary equipment, and enables unified data acquisition and transmission.
Internal SOE transmission delay is less than 200ms, and the response success rate to the control center exceeds 99%.
Supports up to 1024 IEDs and 32 control centers, with a database capacity exceeding 200,000 signals.
Standard | IEC60225-1: 2009 |
Mounting Way | Flush mounted |
Merchanical size (width×high×deepth) | 438mm×288mm×88mm |
Housing material | Metallic plates, parts and screws: Steel Plastic parts: Polycarbonate |
Protection class | Front side:IP40 Rear side, connection terminals: IP20 Other Sides: IP40 |
Communication Ports | 6/12 Ethernet ports 8 RS-485 serial ports |
Communication Protocol | Standard package for server: IEC 60870-5-101/104, DNP, Modbus Standard package for client: IEC 60870-5-101/104, IEC 60870-5-103, DNP3.0 Serial, DNP3.0 LAN/WAN, DNP secure, Modbus serial, Modbus TCP/IP Advanced package: IEC 61850 server & client Customized package: Other customized protocol |
Time Synchronization | SNTP, lEEE 1588, pulse per second (PPS) and IRlG-B |
Function | Relay information acquisition Measurement & control IED information acquisition Auxiliary IED information acquisition Remote control center communication Signal synthesis Command record and query History event record Double device redundancy strategy Time synchronization On-line maintenance and monitoring Self-diagnostic |