Deployed at plants and stations, the system primarily comprises components such as the auxiliary equipment monitoring host, workstations, service gateway machines, and monitoring terminals. It integrates various subsystems—including online monitoring, fire protection, security protection, environmental monitoring, SF6 monitoring, lighting control, and intelligent lock control—to achieve functions such as data acquisition, operational monitoring, control, time synchronization, authorization management, configuration, data storage, reporting, and intelligent linkage management. This system provides auxiliary information support for the integrated monitoring of plants and stations, realizing full situational awareness of their auxiliary equipment, interconnected information sharing, user-friendly human-machine interaction, and significant improvements in operational and inspection efficiency. The system is applicable to the monitoring and control of auxiliary equipment in multiple sectors, including electric power, metallurgy, petroleum, chemical, gas, and railway industries.
Provides station-wide overviews, multi-dimensional data display, hierarchical alarms, and a visualization operation interface, supporting various monitoring methods including floor plans and 3D models.
Supports the configuration of various linkage strategies between main and auxiliary equipment and subsystems, such as alarm-triggered video or environmental threshold-triggered equipment actions, enabling automatic responses.
The system integrates subsystems such as online monitoring, firefighting, security, power environment, and intelligent lock control, achieving comprehensive one-stop monitoring of auxiliary equipment at the plant station.
The system employs a modular design, supports dual-machine redundancy, and ensures high availability with key indicators like 100% control accuracy rate and MTBF exceeding 50,000 hours.
Processor | Dual processor, 64 bit word length, clock speed ≥ 1.8GHz, ≥ 4 cores |
Memory | ≥16GB |
Hard disk | ≥1TB |
Ethernet Port | 4个100M/1000M |
Power | Dual hot swappable redundant power supply |
Screen switching response time | Real time screen ≤ 1s, other screens ≤ 2s |
Signal delay | Alarm signal delay ≤ 1s, control response time ≤ 1s |
Response time for switching between primary and backup machines | ≤30s |
CPU load | Under normal circumstances (within any 30 minutes) ≤ 30%, during emergencies (within 10 seconds) ≤ 50% |
Historical storage | Historical storage time ≥ 3 years |
Function | Data Acquisition Data Processing Operation Monitoring Operation Control Authority Management Time Synchronization Management Configuration Management Data Storage Report Management Intelligent Linkage Remote Transmission Function |