PRS-7741 is specifically designed for monitoring and controlling all types of apparatus in power systems, including circuit breaker, disconnector, earthing switch, etc. Additionally, it is integrated with tap changer control functions for transformer and shunt reactor as well.
This relay can sample the analog values from the traditional instrument transformers, or receive the sampled values from the electronic current and voltage transformers (via a merging unit). The binary inputs and outputs of this relay can be configured according to the demands of a practical engineering through the PRS IED Studio configuration tool auxiliary software, which can meet some special requirements of protection and control functions.
PRS-7741 is suitable to be applied in Substation Automation System (abbreviated as SAS) using different kinds of communication protocol, including IEC-61850 ED1 or ED2. It can also send/receive generic object oriented substation event (abbreviated as GOOSE) message in process level, which make it completely meet the demands of a modern digitalized substation.
Equipped with complete event recording functions for SOE, alarms, and operations, which is crucial for incident analysis, operation traceability, and equipment status monitoring.
Comprehensively supports mainstream communication protocols, including IEC61850 (with GOOSE), and enables data interaction with master stations via Ethernet and RS-485 serial ports.
Seamlessly integrates five functions—measurement, control, telemetry, merging unit, and remote module—significantly enhancing device integration and system reliability.
A robust hardware platform built on a 32-bit dual-core processor, high-speed bus, and intelligent I/O ports lays a solid foundation for data processing.
Utilizes 16-bit A/D converters and dual-channel sampling technology to ensure sampling accuracy; supports both traditional instrument transformer and electronic transformer input modes.
Features a front-mounted LCD screen, keyboard, and indicator lights, providing an intuitive and user-friendly HMI for configuration and monitoring, ensuring ease of operation and maintenance.
Standard | IEC 60529:2013 |
Mounting Way | Flush mounted |
Merchanical size (width×high×deepth) | 1/2 19” Case: 260mm*266 mm *217.7 mm 1/1 19” Case:482.6mm*266 mm *217.7 mm |
Housing material | Metallic plates, parts and screws: Steel Plastic parts: Polycarbonate |
Protection class | Front side:IP40 (IP52 with seal strip) Rear side, connection terminals: IP20 Other Sides: IP40 |
Communication Ports | 3 Ethernet ports 2 RS-485 serial ports |
Communication Protocol | IEC61850, IEC60870-5-103, DNP3.0 or ModBus. |
Time Synchronization | SNTP, lEEE 1588, pulse per second (PPS) and IRlG-B |
Function | AC analog input (Conventional CT/VT) DC analog input DC analog output Binary input Binary output Duplicated binary outputs Supported CB number for closing synchronism check Programmable interlocking logic output |