The device is used for measurement of synchronous phasor and absolute phase angle of voltage and current at all nodes of the entire system by means of clock synchronization and digital signal processing technologies in accordance with IEEE Standard 1344 - 1995 (R2001) and the Technical Specifications for Real-time Dynamic Monitoring Systems of Power System. It provides necessary original data and realization means for such functions as wide-area monitoring of the entire system, substation automation measurement and control, stability control, and adaptive relay protection.
Employs state-of-the-art LVDS backplane bus technology to enable rapid I/O data exchange and enhance plug-in board resistance to interference and expandability.
Provides transient waveform recording, continuous waveform recording, dynamic data recording, and subsynchronous oscillation monitoring functionalities, complying with prevalent international and national standards.
Ensures interoperability by following IEEE Std 1344/IEEE C37.118 and domestic standards, allowing effective transmission and sharing of information to a WAMS (Wide Area Monitoring System) master station.
Leverages 100M Ethernet and multithreading technology to support high-speed transmission of synchronous phasor data
The measurement error of phase and internal potential angle is controlled within 0.2°
Utilizes high-precision GPS clock and oven-controlled crystal oscillator to achieve time synchronization error < 1 µs; clock holdover error < 55 µs even after losing the GPS signal for 60 minutes.
Mounting Way | Flush mounted |
Merchanical size (width×high×deepth) | 258.9mm×177.0mm×283.0mm |
Communication Ports | 4 Ethernet ports |
Communication Protocol | IEC61850, IEEE 1344, IEEE C37.118 |
Time Synchronization | Pulse per second (PPS) and IRlG-B |
Function | Synchronous Phasor Measurement PMU Acquisition Unit Function Self-diagnostic Device power supply supervision |