The primary applications of the intelligent drop-out fuse include mining and oil fields, rural grid upgrades, agricultural irrigation, new energy vehicle charging stations, railway and highway systems, telecommunication base stations, and other 12/24kV terminal distribution substations.
It integrates intelligent current monitoring, switching status indication, temperature detection, short-circuit alarm functions, and wireless data transmission capabilities.
The system integrates multiple sensors to continuously monitor key parameters such as contact temperature, current, and switch position from primary equipment. All data is transmitted in real-time to the master station, enabling remote status monitoring without on-site inspections. This significantly reduces routine maintenance workload. The system also automatically alerts operators upon detecting any abnormal data for prompt troubleshooting.
High-voltage switching operations can be performed remotely, eliminating the need for climbing or working at height. This ensures operators maintain a safe distance from high-voltage equipment, guaranteeing personal safety.
It is immune to operator skill level and prevents misuse, while also meeting all-weather operational requirements unaffected by wind, rain, fog, or darkness.
Item | Unit | Parameters | ||
Rated voltage | kV | 12 | 24 | |
Rated current | A | ≤200 | ||
Drop-out current | A | ≤16 | ||
The minimum distance | mm | 380 | 530 | |
The motor voltage | V(DC) | 24 | ||
Lightning impulse withstand voltage | kV | 75/85 | 150 | |
Power frequency withstand voltage | kV | 42/48 | 65 | |
Charging Voltage | V | AC 100-250 | ||
Controller Standby Power Consumption | W | 0.4 | ||
Current Measurement | Range | A | 0-200 | |
Accuracy | % | (10%-2000%)×ln≤3% | ||
Contact Temperature Measurement | Range | ℃ | -25~100 | |
Accuracy | ℃ | not exceed±1 | ||
Oil Temperature Measurement | Range | ℃ | -40~120 | |
Accuracy | ℃ | not exceed±2 | ||
Oil Pressure Measurement | Range | kPa | -30~130 | |
Accuracy | kPa | not exceed±2 | ||