QWD safety and stability control master station (The Second Level) equipment includes a distributed stability control host QWD-MMB-G and a distributed stability control slave QWD-SMB-G, which are used together. The stability control master station has the ability to connect 12 lines and 4 main transformers by expanding slave. Each slave should have the ability to connect 4 lines or 2 main transformers.
QWD safety and stability control new energy executive station equipment includes a distributed stability control host QWD-MEC-G and a distributed stability control slave QWD-SEC-G, which are used together. The stability control new energy executive station shall have the ability to connect with 4 main transformers and 18 gathering line circuits.
Utilizes 64-bit floating-point SOC chips and a real-time operating system, featuring reliable technology, easy maintenance/upgrading, and strong compatibility.
The protection core and blocking core have independent starting elements. The entire equipment outputs only when both elements are active, ensuring high safety.
Adopts a master-slave structure (1 master, 1-5 slaves). Hardware and software are modularized/standardized, allowing flexible configuration and expansion on demand.
The station level supports 3 independent Ethernet interfaces (IEC61850), uses fiber optic communication, and modular programs facilitate configuration and debugging.
Mounting Way | Flush mounted |
Merchanical size (width×high×deepth) | 482.6mm x 177mm x 278mm |
Communication Ports | 3 Ethernet ports |
Communication Protocol | IEC60870-5-103/104, IEC61850 |
Time Synchronization | PPS, PPM, IRIG-B |
Function | Variable start and remote command start element Element on/off Judgement Criterion Fault Type Judgement Criterion Protection Tripping Input Abnormal Alarm Switch Position Signal Abnormal Alarm The Other Equipment Action Input Abnormal Alarm Self-diagnostic Device power supply supervision |